NEMA TC-7
Our HDPE conduit made in accordance with requirements of NEMA TC-7 and is ideal for the installation and protection of electrical cables underground.
Features
- Available from ½" to 12"
- Manufactured from flexible HDPE, makes gradual bends without special equipment
- Continuous lengths reduce joining costs
- Excellent low-temperature properties, allows installation in cold climates
- Outstanding long-term cable protection from shifting ground, rock, and root impingement
- Provides a permanent pathway, simplifies future cable repairs or replacement
- Can be encased in concrete
Details
- Footage/Meter Markings
Specifications and Shipping Info
Choose Conduit Size, Wall Type, and Wall Ratio
Nominal Size
Wall Type
Wall Ratio
Product specifications
Nominal OD (in.)
0.84
Nominal OD (mm)
21.34
OD Tolerance (in.)
0.004
OD Tolerance (mm)
0.11
Wall Tolerance + (in.)
0.02
Wall Tolerance + (mm)
0.51
Min. Wall (in.)
0.147
Min Wall (mm)
3.73
Min. ID (in.)
0.506
Min. ID (mm)
12.9
Avg ID (in.)
0.526
Avg ID (mm)
13.4
Weight (g/m)
209
Bend Radius Supported (mm)
213
Bend Radius Unsupported (mm)
320
Conduit SWPS (kg)
332
Reel specifications
50 x 46
5000
Steel
66 x 46
10000
Steel
Downloads
Colors
UV Gray
UV Red
UV Black
Installations
Applications
- Electrical